PSS18/24-40-CAN |
PSS18/48-30-CAN |
PSS18/60-25-CAN |
PSS18/110-13.3-CAN |
PSS18/220-6.7-CAN |
PSS18/220-6.7 Relay |
Article code |
100-018-140.00 |
100-018-150.00 |
100-018-160.00 |
100-018-170.00 |
100-018-180.00 |
100-018-180.09 |
Nominal input voltage |
230VAC |
Nominal input current |
5.2AAC |
7.9AAC |
7.9AAC |
7.9AAC |
7.9AAC |
7.9AAC |
Input frequency range |
47– 63Hz |
Power factor |
>0.95 at Pnom <25% ; >0.97 at 50% >Pnom >25% ; >0.99 at 100% >Pnom >50% |
Efficiency |
≥90% |
≥91% |
≥91% |
≥91% |
≥91% |
≥91% |
Internal input fusing |
MCB B10A |
Nominal output voltage |
24VDC |
48VDC |
60VDC |
108VDC |
216VDC |
216VDC |
Nominal output current |
40.0ADC |
30.0ADC |
25.0ADC |
13.3ADC |
6.7ADC |
6.7ADC |
Charge characteristic line |
IV line acc. to DIN 41772/DIN 41773 |
Output voltage V01 (Trickle charging) |
27.2VDC ±1% (23.4 to 28.8V adjustable) |
54.5VDC ±1% (46.6 to 57.6V adjustable) |
68.1VDC ±1% (58.5 to 72V adjustable) |
122.6VDC ±1% (105 to 130V adjustable) |
245.2VDC±1% (211 to 260V adjustable) |
245.2VDC±1% (211 to 260V adjustable) |
Output voltage V02 (Boost charging) |
28.8VDC ±1% (24 to 30V adjustable) |
57.6VDC ±1% (48 to 60V adjustable) |
72.0VDC ±1% (60 to 73V adjustable) |
129.6VDC ±1% (108 to 135V adjustable) |
259.2VDC±1% (216 to 270V adjustable) |
259.2VDC±1% (216 to 270V adjustable) |
Output voltage V02 (Boost charging) |
22.2VDC ±1% (20.4 to 24V adjustable) |
44.4VDC ±1% (40.8 to 48V adjustable) |
55.5VDC ±1% (51 to 60V adjustable) |
99.9VDC ±1% (91.8 to 108V adjustable) |
200VDC ±1% (184 to 216V adjustable) |
200VDC ±1% (184 to 216V adjustable) |
Voltage ripple |
≤20mVss |
≤20mVss |
≤20mVss |
≤100mVss |
≤200mVss |
≤200mVss |
Psophometric acc. to CCITT-A |
≤1.2mVeff |
≤1.8mVeff |
≤1.8mVeff |
- - - |
- - - |
- - - |
Dynamic accuracy of the charging voltage |
<3% Vnom at load transients between 10% - 90% - 10% Inom, recovery time t≤1 ms |
Short circuit protection |
Continuously short circuit proof, 1x Inom |
Parallel operation |
Yes, <20 pieces, load sharing appr. 10% Inom |
Internal decoupling at the output |
optional |
LED signalling |
Mains O.K. (green); VO1 (green); VO2 (green); I0 (yellow); V< (green); V> (red); Alarm (red) |
Digital displays |
Output voltage, output current |
Monitoring |
Output voltage high/low, output voltage, output current, short circuit |
External functions |
Active current sharing, boost charge and battery test function, temperature compensation of the charging voltage, external |
sensor lead for the output voltage, remote ON/OFF, optocoupler signal “VO O.K.“, “Mains O.K.” and “Constant current operation” |
Communications interface |
CAN-bus interface for communication with central monitoring unit (MU1000C, optional) |
Ambient temperature |
Operation: -20°C to +55°C, storage: -40°C to +85°C |
Climatic conditions |
Climatic conditions |
Max. installation altitude // Audible noise |
<1000 m // <40 dB (A) in 1 m distance |
Construction |
1/3-19“ plug-in module for mounting in sub racks acc. to DIN 41 494, front connectors |
Dimensions ( W/H/D) //Weight |
142/262/287 mm //app. 7.6 kg |
Cooling |
Natural convection |
Type of enclosure / Protection class |
IP20 (mech.); 1 (electr.) |
Surfaces |
Front panel: powder coating RAL 7035, constructive parts: anodised |
CE conformity |
yes |
Compliance to safety standards |
EN 60950-1, VDE 0100 part 410, VDE 0110, EN 50178, EN 60146 |
Compliance to EMC standards |
EN 55011, EN 55022 class „B“, EN 61000– 4 part 2– 5 |