Type |
PSC18/x/24-40-CAN |
PSC18/x/48-30-CAN |
PSC18/x/60-25-CAN |
PSC18/x/110-13.4-CAN |
PSC18/x/220-6.7-CAN |
PSC18/x/220-6.7 Relay |
Код заказа x=110 |
200-018-740.00 |
200-018-750.00 |
200-018-760.00 |
200-018-770.00 |
200-018-780.00 |
200-018-780.09 |
Код заказа x=220 |
200-018-840.00 |
200-018-850.00 |
200-018-860.00 |
200-018-870.00 |
200-018-880.00 |
- - - |
Nominal input voltage |
110VDC & 220VDC +15/-20%; according to the article codes |
Nominal input current @110VDC/220VDC |
9.8/4.9ADC |
14.5/7.3ADC |
15.2/7.6ADC |
14.9/7.4ADC |
14.9/7.4ADC |
14.9/7.4ADC |
Efficiency |
≥90% |
≥91% |
≥91% |
≥91% |
≥91% |
≥91% |
Internal input fusing |
16A gL |
Nominal output voltage |
24VDC |
48VDC |
60VDC |
110VDC |
220VDC |
220VDC |
Nominal output current |
40.0ADC |
30.0ADC |
25.0ADC |
13.4ADC |
6.7ADC |
6.7ADC |
Adjustable range |
20-40A |
15-30A |
12.5-25A |
6.7-13.4A |
3.4-6.7A |
3.4-6.7A |
Charging characteristic line |
IV-line acc. to DIN 41772/DIN 41773 |
Output voltage V01 (trickle charging) |
27.2VDC ±1%(23.4 to 28.8V adjustable) |
54.5VDC±1%(46.6 to 57.6V adjustable) |
68.1VDC ±1%(58.5 to 72V adjustable) |
122.6VDC ±1%(105 to 130V adjustable) |
245.2VDC ±1%(211 to 260V adjustable) |
245.2VDC ±1%(211 to 260V adjustable) |
Output voltage V02 (boost charging) |
28.8VDC ±1%(24 to 30V adjustable) |
57.6VDC±1%(48 to 60V adjustable) |
72.0VDC ±1%(60 to 73V adjustable) |
129.6VDC ±1%(108 to 135V adjustable) |
259.2VDC ±1%(216 to 270V adjustable) |
259.2VDC ±1%(216 to 270 V adjustable) |
Output voltage V03 (Battery test) |
22.2VDC ±1%(20.4 to 24V adjustable) |
44.4VDC±1%(40.8 to 48V adjustable) |
55.5VDC ±1%(51 to 60V adjustable) |
99.9VDC±1%(91.8 to 108V adjustable) |
200VDC ±1%(184 to 216V adjustable) |
200VDC ±1%(184 to 216V adjustable) |
Voltage ripple |
≤ 20mVpp |
≤ 20mVpp |
≤ 20mVpp |
≤ 100mVpp |
≤ 200mVpp |
≤ 200mVpp |
Psophometric acc. to CCITT-A |
≤ 1.2mVrms |
≤ 1.8mVrms |
≤ 1.8mVrms |
- - - |
- - - |
- - - |
Dynamic accuracy of the charging voltage |
< 3% Vnom at load transients between 10% - 90% - 10% Inom, recovery time t ≤ 1.5ms |
Short circuit protection |
Continuous short circuit proof, 1x Inom |
Parallel operation |
Yes, <20 pieces, load sharing appr. 10% Inom |
Internal decoupling at the output |
no |
LED signalling |
Input O.K. (green); V01 (green); V02 (green); I0 (yellow); V< (green); V> (red); Alarm (red) |
Digital displays |
Output voltage, output current |
Isolated signalling contacts |
“General fault” and “V0<“ |
Monitoring |
Output voltage high/low, output voltage, output current, short circuit |
External functions |
Active current sharing, boost charge and battery test function, temperature compensation of the charging voltage, external sensor lead for the output voltage, remote ON/OFF, optocoupler signal “V0 O.K.“, “Mains O.K.” and “Constant current operation” |
Communications interface |
CAN-Bus interface for communication with central monitoring unit (MU1000C, optional) - - - |
Ambient temperature |
Operation: -20°C to +45°C, storage: -40°C to +85°C |
Climatic conditions |
IEC 721-3-3 class 3K3/3Z1/3B1/3C2/3S2/3M2 |
Max. installation altitude |
<1500m |
Audible noise |
< 30dB (A) in 1m distance |
Construction |
1/3 x19“ module, 6U for mounting in sub racks acc. to DIN 41 494, front connectors |
Dimensions (W/H/D) |
142/262/287mm |
Weight approx. |
8.4kg |
Cooling |
Natural convection |
Type of enclosure / Protection class |
IP20 (mech.) / 1 (electr.) |
Surfaces |
Front panel: powder coating RAL 7035, black imprint; constructive parts: anodized |
CE conformity |
yes |
Compliance to safety standards |
EN 60950-1, VDE 0100 part 410, VDE 0110, EN 50178, EN 60146 |
Compliance to EMC standards |
EN 55011, EN 55022 class „B“, EN 61000– 4 part 2– 5 |